IECC R402 — Building Thermal Envelope (Residential)

Updated Mar 25, 2026
Insulation R-values and fenestration U-factors by climate zone for residential buildings.

IECC 2024: Zone 1: ceiling R-30, wall R-13, window U-0.40. Zone 3: ceiling R-38, wall R-20 or 13+5ci, window U-0.32. Zone 4: ceiling R-49, wall R-20 or 13+5ci, window U-0.30. Zone 6: ceiling R-49, wall R-20+5ci or 13+10ci, window U-0.30. Air barrier ≤3 ACH50 Zones 3-8.

TAGS
IECCinsulationR-valueclimate-zoneenergy-code
DETAILS
code year
2024
code system
IECC
code section
R402
RELATED KNOWLEDGE
📋 Code
IBC 903.2.1 — Group A Occupancies (Sprinkler Requirements)
Automatic sprinkler system required throughout buildings with Group A occupancy where fire area exceeds 5,000 square feet, or overall building area exceeds 12,000 square feet, or occupant load of the fire area exceeds 300.
📋 Code
IBC 903.2.7 — Group M Occupancies (Retail Sprinkler Requirements)
Automatic sprinkler system required in Group M (mercantile) occupancies where fire area exceeds 12,000 square feet or building is more than three stories above grade.
📋 Code
IBC 903.2.11.3 — Buildings 55 Feet or More in Height
Automatic sprinkler system required throughout buildings with a floor level having an occupant load of 30 or more that is located 55 feet or more above the lowest level of fire department vehicle access.
📋 Code
IBC 1015.1 — Exit and Exit Access Doorways Required
Two exits or exit access doorways required from any space where occupant load exceeds the table values. Spaces with occupant load exceeding 500 require a minimum of 3 exits. Spaces exceeding 1,000 require 4 exits.
📋 Code
IBC 1017.2 — Exit Access Travel Distance
Maximum travel distance from any point in a building to an exit shall not exceed 200 feet unsprinklered or 250 feet sprinklered for most occupancies. Specific occupancies have modified limits.
📋 Code
IBC Table 601 — Fire-Resistance Rating Requirements
Specifies minimum fire-resistance ratings for structural elements based on construction type (Type I through V). Type IA requires 3-hour rated structural frame, 2-hour floors, and 1.5-hour roof.