IECC C405 — Commercial Lighting (AZ / NV)

Updated May 18, 2026
IECC commercial lighting controls + LPD limits adopted by Phoenix and Las Vegas.

IECC §C405 (2018, as adopted by Phoenix and Las Vegas) governs commercial lighting. Maximum LPD by space type: open office 0.74 W/sf, retail 1.05 W/sf, warehouse 0.45 W/sf, parking garage 0.21 W/sf. Automatic controls: occupancy sensors required in private offices, conference rooms, storage; daylight responsive controls in sidelit zones with >150 W of lighting; receptacle automatic shutoff in offices. Phoenix amends with §C407 as alternative compliance path for buildings >50,000 sf.

TAGS
commercial-officelightingLPDIECC
DETAILS
edition
2018
use case
["commercial-office","retail","warehouse"]
adopted by
["az-statewide","nv-statewide","az-phx","nv-lv","az-mesa","nv-henderson"]
code system
IECC
confidence tier
primary
SOURCES
🔗https://codes.iccsafe.org/content/IECC2021P1
RELATED KNOWLEDGE
📋 Code
IMC Chapter 6 — Duct Systems
Duct materials, SMACNA construction, fire/smoke dampers, flex duct, plenum requirements.
📋 Code
IMC Chapter 10 — Boilers, Water Heaters, Pressure Vessels
Boiler rooms, clearances, T&P relief valves, expansion tanks, combustion air requirements.
📋 Code
IMC Chapter 5: Exhaust Systems
Technical requirements for imc chapter 5: exhaust systems.
📋 Code
IMC Chapter 6: Duct Systems
Technical requirements for imc chapter 6: duct systems.
📋 Code
IMC Chapter 7: Combustion Air
Technical requirements for imc chapter 7: combustion air.
📋 Code
IMC Chapter 8: Chimneys and Vents
Technical requirements for imc chapter 8: chimneys and vents.
← Back to Knowledge Garden