IBC Chapter 10 — Means of Egress (Complete)

Updated Mar 25, 2026
Comprehensive requirements for exit design including occupant load, number of exits, exit widths, travel distances, exit signs, emergency lighting, and accessible means of egress.

Section 1004: Occupant load — calculated by floor area / occupant load factor (Table 1004.5). Assembly standing: 5 sf/person. Business: 150 sf/person. Educational: 20 sf/person. Section 1005: Means of egress sizing — 0.3 in/person for stairways, 0.2 in/person for other components. Section 1006: Number of exits — 1-500 occupants = 2 exits, 501-1000 = 3, >1000 = 4. Single exit permitted for OL ≤49 with limited travel distance. Section 1007: Exit and exit access doorway configuration — separation of exits by 1/2 diagonal in sprinklered, 1/3 in non-sprinklered. Section 1017: Exit access travel distance — max 200 ft non-sprinklered, 250 ft sprinklered for most occupancies. Group H: 75-100 ft. Section 1020: Corridors — min 44 in wide (36 in for OL<50). 1-hr rated or 0.5-hr in sprinklered. Section 1023: Interior exit stairways — 2-hr in 4+ stories, 1-hr in less. Min 44 in wide (36 in for OL<50). Section 1013: Exit signs — illuminated, visible from 100 ft, at required exits and along exit access path. Section 1008: Accessible means of egress — at least 2 per story, areas of refuge per Section 1009.

TAGS
IBCegressexittravel-distanceoccupant-loadexit-signemergency-lightingstairway
DETAILS
tables
["1004.5","1006.3.1"]
code year
2024
code system
IBC
code section
Chapter 10
RELATED KNOWLEDGE
📋 Code
IBC 903.2.1 — Group A Occupancies (Sprinkler Requirements)
Automatic sprinkler system required throughout buildings with Group A occupancy where fire area exceeds 5,000 square feet, or overall building area exceeds 12,000 square feet, or occupant load of the fire area exceeds 300.
📋 Code
IBC 903.2.7 — Group M Occupancies (Retail Sprinkler Requirements)
Automatic sprinkler system required in Group M (mercantile) occupancies where fire area exceeds 12,000 square feet or building is more than three stories above grade.
📋 Code
IBC 903.2.11.3 — Buildings 55 Feet or More in Height
Automatic sprinkler system required throughout buildings with a floor level having an occupant load of 30 or more that is located 55 feet or more above the lowest level of fire department vehicle access.
📋 Code
IBC 1015.1 — Exit and Exit Access Doorways Required
Two exits or exit access doorways required from any space where occupant load exceeds the table values. Spaces with occupant load exceeding 500 require a minimum of 3 exits. Spaces exceeding 1,000 require 4 exits.
📋 Code
IBC 1017.2 — Exit Access Travel Distance
Maximum travel distance from any point in a building to an exit shall not exceed 200 feet unsprinklered or 250 feet sprinklered for most occupancies. Specific occupancies have modified limits.
📋 Code
IBC Table 601 — Fire-Resistance Rating Requirements
Specifies minimum fire-resistance ratings for structural elements based on construction type (Type I through V). Type IA requires 3-hour rated structural frame, 2-hour floors, and 1.5-hour roof.
← Back to Knowledge Garden