IMC Chapter 4 — Ventilation

Updated Mar 25, 2026
Mechanical ventilation requirements: outdoor air rates, exhaust, duct systems, and air quality.

IMC 2024 Ch4: Section 401 — ventilation required where natural ventilation per IBC 1203 is not provided. Section 403 — outdoor air: ASHRAE 62.1 rates. Office: 5 cfm/person + 0.06 cfm/sf. Classroom: 10 cfm/person + 0.12 cfm/sf. Retail: 7.5 cfm/person + 0.06 cfm/sf. Section 401.3 — economizer required per IECC when applicable. Section 502 — exhaust rates: commercial kitchen Type I hood (400 cfm/linear ft min), bathrooms (50 cfm intermittent or 20 cfm continuous), parking garages (0.75 cfm/sf). Section 504 — duct systems: materials per UL 181/181A/181B, support at intervals per material type, fire dampers at rated assemblies. Section 505 — return air: not from hazardous, toilet, kitchen, storage, or parking areas.

TAGS
IMCventilationoutdoor-airexhaustASHRAE-62.1
DETAILS
code year
2024
code section
Chapter 4
RELATED KNOWLEDGE
📋 Code
IBC 903.2.1 — Group A Occupancies (Sprinkler Requirements)
Automatic sprinkler system required throughout buildings with Group A occupancy where fire area exceeds 5,000 square feet, or overall building area exceeds 12,000 square feet, or occupant load of the fire area exceeds 300.
📋 Code
IBC 903.2.7 — Group M Occupancies (Retail Sprinkler Requirements)
Automatic sprinkler system required in Group M (mercantile) occupancies where fire area exceeds 12,000 square feet or building is more than three stories above grade.
📋 Code
IBC 903.2.11.3 — Buildings 55 Feet or More in Height
Automatic sprinkler system required throughout buildings with a floor level having an occupant load of 30 or more that is located 55 feet or more above the lowest level of fire department vehicle access.
📋 Code
IBC 1015.1 — Exit and Exit Access Doorways Required
Two exits or exit access doorways required from any space where occupant load exceeds the table values. Spaces with occupant load exceeding 500 require a minimum of 3 exits. Spaces exceeding 1,000 require 4 exits.
📋 Code
IBC 1017.2 — Exit Access Travel Distance
Maximum travel distance from any point in a building to an exit shall not exceed 200 feet unsprinklered or 250 feet sprinklered for most occupancies. Specific occupancies have modified limits.
📋 Code
IBC Table 601 — Fire-Resistance Rating Requirements
Specifies minimum fire-resistance ratings for structural elements based on construction type (Type I through V). Type IA requires 3-hour rated structural frame, 2-hour floors, and 1.5-hour roof.
← Back to Knowledge Garden