Fire Sprinkler Head — Pendent (155°F Standard)

Updated Mar 26, 2026
Standard spray pendent sprinkler for concealed or exposed ceiling grid. UL/FM listed.

Pendent sprinkler: hangs below ceiling (most common type). Activation: 155F ordinary temperature rating fusible link or glass bulb. Coverage: standard spray 15x15 ft max (225 sf) per NFPA 13 Table 8.6.2.2.1. K-factor: 5.6 (standard), 8.0 (large orifice for high-challenge). Thread: 1/2in or 3/4in NPT. Deflector: below ceiling plane — distributes water in umbrella pattern. Concealed type: flat cover plate (activates before sprinkler, drops to expose head). Quick-response: 3mm glass bulb (vs 5mm standard) — required in light hazard, residential. ESR: early suppression fast response — high-challenge storage. Temperature ratings: ordinary 135-170F, intermediate 175-225F (near heat sources), high 250-300F. Install within 1in of ceiling (max 18in per NFPA 13). Escutcheon covers ceiling plate. Cost: $5-$25 each. CSI 21 13 13.

TAGS
sprinklerfire-protectionNFPA-13pendentfusible-linkUL
DETAILS
coverage
225 sf max
k factor
5.6
temperature
155F
csi division
21 13 13
RELATED KNOWLEDGE
🧱 Material
Concrete — 4,000 PSI Normal Weight
Standard structural concrete mix with 4,000 psi compressive strength at 28 days, 150 pcf unit weight. Most common mix for foundations, slabs, columns, and beams in commercial and residential construction.
🧱 Material
Structural Steel — ASTM A992 (W-shapes)
Standard structural steel for wide-flange shapes (W-beams, W-columns). 50 ksi yield strength, 65 ksi tensile strength. The dominant steel grade for structural framing in commercial construction.
🧱 Material
Lumber — SPF 2x4 Stud Grade (Spruce-Pine-Fir)
Standard dimensional lumber for wall framing. Actual dimensions 1.5 x 3.5 inches. Available in 8, 10, 12, 16 foot lengths. Stud grade meets IBC requirements for bearing walls up to 10 feet.
🧱 Material
Romex NM-B 12/2 — Non-Metallic Sheathed Cable (Residential Wiring)
Standard residential electrical wiring: 12 AWG copper, 2 conductors + ground, NM-B rated. For 20-amp circuits. Used for kitchen, bathroom, laundry, garage receptacles per NEC. Interior dry locations only.
🧱 Material
Gypsum Board — 5/8" Type X (Fire-Rated)
Fire-rated gypsum wallboard providing 1-hour fire resistance when applied to each side of a wood or steel stud wall. Required by IBC for fire-resistance-rated assemblies. 4x8 and 4x12 sheets standard.
🧱 Material
Reinforcing Steel — Grade 60 Deformed Bar (#4 through #11)
Standard reinforcing steel for concrete construction. 60,000 psi yield strength. Deformed surface for bond with concrete. Used in foundations, slabs, columns, beams, and walls. Specified per ACI 318.
← Back to Knowledge Garden