HomeKnowledgeNEC Article 240 — Overcurrent Protection
📋 Codecodeselectrical

NEC Article 240 — Overcurrent Protection

Updated Mar 26, 2026
Circuit breaker and fuse sizing: conductor protection, coordination, available fault current marking.

NEC Article 240: 240.4 protection of conductors: overcurrent device rating not to exceed conductor ampacity per Table 310.16. 240.4(D) small conductors: 14 AWG = 15A, 12 AWG = 20A, 10 AWG = 30A. 240.6 standard ampere ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600. 240.21 feeder overcurrent protection at supply end (exceptions for tap rules: 10ft tap, 25ft tap). 240.67 arc energy reduction required for services and feeders >1,200A (maintenance switch or zone-selective interlocking). 240.87 arc energy reduction for breakers rated 1,200A+ (instantaneous trip, zone-selective, energy-reducing).

TAGS
NECovercurrentbreakerfuseconductor-protectionarc-energy
DETAILS
code year
2023
code system
NEC
code section
Article 240
RELATED KNOWLEDGE
📋 Code
IBC 903.2.1 — Group A Occupancies (Sprinkler Requirements)
Automatic sprinkler system required throughout buildings with Group A occupancy where fire area exceeds 5,000 square feet, or overall building area exceeds 12,000 square feet, or occupant load of the fire area exceeds 300.
📋 Code
IBC 903.2.7 — Group M Occupancies (Retail Sprinkler Requirements)
Automatic sprinkler system required in Group M (mercantile) occupancies where fire area exceeds 12,000 square feet or building is more than three stories above grade.
📋 Code
IBC 903.2.11.3 — Buildings 55 Feet or More in Height
Automatic sprinkler system required throughout buildings with a floor level having an occupant load of 30 or more that is located 55 feet or more above the lowest level of fire department vehicle access.
📋 Code
IBC 1015.1 — Exit and Exit Access Doorways Required
Two exits or exit access doorways required from any space where occupant load exceeds the table values. Spaces with occupant load exceeding 500 require a minimum of 3 exits. Spaces exceeding 1,000 require 4 exits.
📋 Code
IBC 1017.2 — Exit Access Travel Distance
Maximum travel distance from any point in a building to an exit shall not exceed 200 feet unsprinklered or 250 feet sprinklered for most occupancies. Specific occupancies have modified limits.
📋 Code
IBC Table 601 — Fire-Resistance Rating Requirements
Specifies minimum fire-resistance ratings for structural elements based on construction type (Type I through V). Type IA requires 3-hour rated structural frame, 2-hour floors, and 1.5-hour roof.
← Back to Knowledge Garden