Two exits or exit access doorways from any space shall be provided where the occupant load exceeds the values in Table 1006.2.1 (typically 49 for most occupancies). Three exits or exit access doorways shall be provided from any space with an occupant load of 501 to 1,000. Four exits or exit access doorways shall be provided from any space with an occupant load greater than 1,000. This is the foundational egress requirement that drives floor plan design for virtually every commercial building.