An automatic sprinkler system shall be provided throughout buildings containing a Group A occupancy where one of the following conditions exists: (1) The fire area exceeds 5,000 square feet. (2) The fire area has an occupant load of 300 or more. (3) The fire area is located on a floor other than a level of exit discharge serving such occupancies. (4) The fire area contains a multitheater complex. For Group A-1 occupancies, sprinklers are required where the fire area exceeds 12,000 sf regardless of occupant load. Amendments: Los Angeles enforces at 3,000 sf for A-2 occupancies. NYC requires sprinklers in all A occupancies regardless of size.