HomeKnowledgeUPC 422.1 — Minimum Plumbing Fixture Count
🌿 code_sectionplumbingplumbing

UPC 422.1 — Minimum Plumbing Fixture Count

Updated May 22, 2026
Required number of water closets, lavatories, urinals, drinking fountains, and service sinks by occupancy and occupant load.

Implementation in src/lib/mep-load-calc.ts calculatePlumbingFixtures(). Note: real UPC 422.1 separates M/F counts; our calc uses a combined ratio for early scoping and flags the simplification.

TAGS
UPC422.1plumbing-fixturesoccupant-loadCPC-Table-4-1
DETAILS
book
UPC 2024
section
422.1
mep calc workflow
q-equipment-schedule
SOURCES
🔗https://codes.iccsafe.org/content/UPC2024P1
RELATED KNOWLEDGE
🌿 code_section
IFC 903 — Automatic Sprinkler Systems
When sprinklers are required by occupancy classification, fire area, height, and water-supply availability. Triggers NFPA 13/13R/13D design.
🌿 code_section
NEC 220.83 — Existing Dwelling Optional Calculation
Alternative load-calc method for existing single dwelling units: first 8 kVA of all loads at 100%, remainder at 40%, plus A/C at 100%.
🌿 code_section
NEC 240.4 — Conductor Overcurrent Protection
Conductors must be protected at their ampacity. 240.4(D) small-conductor rule: 14 AWG max 15A, 12 AWG max 20A, 10 AWG max 30A.
🌿 code_section
NEC 250 — Grounding and Bonding
Governs grounding electrode system, equipment grounding conductor sizing, and bonding requirements at the service. Required for every panel schedule.
🌿 code_section
NEC 220.12 — General Lighting Load by Occupancy
VA-per-square-foot table used as the base general-lighting load in any service-load calc. Office 3.5, dwelling 3.0, restaurant 2.0, warehouse 0.25.
🌿 code_section
CMC 403 / ASHRAE 62.1 — Ventilation Rates for Acceptable IAQ
Outdoor air ventilation rates by occupancy (CFM per person + CFM per sqft). Office 5 + 0.06, retail 7.5 + 0.06, restaurant dining 7.5 + 0.18, etc.
← Back to Knowledge Garden