IBC 302.1 — Occupancy Classification

Updated Mar 25, 2026
Every building or portion thereof shall be classified according to its use or the character of its occupancy. Groups: A (Assembly), B (Business), E (Educational), F (Factory), H (High-Hazard), I (Institutional), M (Mercantile), R (Residential), S (Storage), U (Utility).

The 10 occupancy groups determine nearly every other code requirement — fire protection, means of egress, construction type limits, plumbing fixtures, and accessibility. Group A: Assembly (A-1 theaters, A-2 restaurants/bars, A-3 churches/libraries, A-4 arenas, A-5 outdoor). Group B: Business (offices, banks, clinics). Group E: Educational (K-12 schools). Group F: Factory (F-1 moderate hazard, F-2 low hazard). Group H: High-Hazard (explosives, flammables). Group I: Institutional (I-1 assisted living, I-2 hospitals, I-3 prisons, I-4 daycare). Group M: Mercantile (retail). Group R: Residential (R-1 hotels, R-2 apartments, R-3 houses, R-4 care facilities). Group S: Storage (S-1 moderate hazard, S-2 low hazard). Group U: Utility (barns, greenhouses).

TAGS
occupancyclassificationibc-chapter-3group-agroup-bgroup-r
DETAILS
chapter
3 - Use and Occupancy Classification
severity
prescriptive
code year
2024
code system
IBC
building types
["all"]
section number
302.1
RELATED KNOWLEDGE
📋 Code
IBC 903.2.1 — Group A Occupancies (Sprinkler Requirements)
Automatic sprinkler system required throughout buildings with Group A occupancy where fire area exceeds 5,000 square feet, or overall building area exceeds 12,000 square feet, or occupant load of the fire area exceeds 300.
📋 Code
IBC 903.2.7 — Group M Occupancies (Retail Sprinkler Requirements)
Automatic sprinkler system required in Group M (mercantile) occupancies where fire area exceeds 12,000 square feet or building is more than three stories above grade.
📋 Code
IBC 903.2.11.3 — Buildings 55 Feet or More in Height
Automatic sprinkler system required throughout buildings with a floor level having an occupant load of 30 or more that is located 55 feet or more above the lowest level of fire department vehicle access.
📋 Code
IBC 1015.1 — Exit and Exit Access Doorways Required
Two exits or exit access doorways required from any space where occupant load exceeds the table values. Spaces with occupant load exceeding 500 require a minimum of 3 exits. Spaces exceeding 1,000 require 4 exits.
📋 Code
IBC 1017.2 — Exit Access Travel Distance
Maximum travel distance from any point in a building to an exit shall not exceed 200 feet unsprinklered or 250 feet sprinklered for most occupancies. Specific occupancies have modified limits.
📋 Code
IBC Table 601 — Fire-Resistance Rating Requirements
Specifies minimum fire-resistance ratings for structural elements based on construction type (Type I through V). Type IA requires 3-hour rated structural frame, 2-hour floors, and 1.5-hour roof.