Table 504.4 sets maximum height limits based on construction type. Key values — Type IA: unlimited height for A/B/E/F/M/S, 12 stories for R. Type IB: 180 ft for B, 11 stories for R. Type IIA: 85 ft for B, 5 stories for R. Type IIB: 75 ft for B, 4 stories for R. Type IIIA: 85 ft for B, 4 stories for R. Type IIIB: 75 ft for B, 4 stories for R. Type IV-A (mass timber): 270 ft / 18 stories. Type VA: 60 ft for B, 3 stories for R. Type VB: 40 ft for B, 2 stories for R. Automatic sprinklers per 903.3.1.1 add 1 story and 20 feet to allowable height. This table drives the fundamental decision of what construction type is needed for a given building program.