Section 504: Building height — Table 504.3 provides maximum height in feet by occupancy and construction type. Type IA: unlimited for B, F, M, S. Type IIA: 65-85 ft depending on occupancy. Section 506: Allowable area — Table 506.2 provides maximum area per story by occupancy and type. Unlimited area: 1-story sprinklered buildings of Type IIB or higher with 60 ft frontage and fire-department access. Section 504.2: Automatic sprinkler increase — add 20 ft to allowable height for NFPA 13 systems. Section 506.3: Frontage increase — percentage increase based on frontage on public way or open space >20 ft wide. Section 507: Unlimited area buildings — 1-story, sprinklered, 60 ft access. Section 510: Special provisions — podium buildings (Type IA 1st story + lesser above), horizontal/vertical building separations.