IBC Chapter 7 — Fire and Smoke Protection Features

Updated Mar 25, 2026
Fire-resistance-rated construction requirements: fire walls, fire barriers, fire partitions, smoke barriers, smoke partitions, horizontal assemblies, shaft enclosures, and opening protectives.

Section 703: Fire-resistance rating and testing — ratings determined by ASTM E119 or UL 263. Section 706: Fire walls — structural stability, minimum 2-hr rating (3-hr or 4-hr for certain occupancies). Each side independently stable. Section 707: Fire barriers — occupancy separations, shaft enclosures, exit enclosure walls. 1-hr minimum for most uses, 2-hr for occupancy separations, 2-hr for shafts in 4+ stories. Section 708: Fire partitions — corridor walls, dwelling unit separations. 1-hr in sprinklered buildings, 0.5-hr for certain dwellings. Section 709: Smoke barriers — continuous membrane, 1-hr rated, hospital smoke compartments. Section 710: Smoke partitions — corridor smoke, not required to be fire rated. Section 711: Horizontal assemblies — floor/ceiling and roof/ceiling assemblies maintaining fire resistance. Section 713: Shaft enclosures — 2-hr for shafts in 4+ stories, 1-hr for others. Section 716: Opening protectives — fire doors, fire shutters, fire windows rated by NFPA 252/257.

TAGS
IBCfire-wallfire-barrierfire-partitionsmoke-barriershaft-enclosureopening-protective
DETAILS
code year
2024
code system
IBC
code section
Chapter 7
RELATED KNOWLEDGE
📋 Code
IBC 903.2.1 — Group A Occupancies (Sprinkler Requirements)
Automatic sprinkler system required throughout buildings with Group A occupancy where fire area exceeds 5,000 square feet, or overall building area exceeds 12,000 square feet, or occupant load of the fire area exceeds 300.
📋 Code
IBC 903.2.7 — Group M Occupancies (Retail Sprinkler Requirements)
Automatic sprinkler system required in Group M (mercantile) occupancies where fire area exceeds 12,000 square feet or building is more than three stories above grade.
📋 Code
IBC 903.2.11.3 — Buildings 55 Feet or More in Height
Automatic sprinkler system required throughout buildings with a floor level having an occupant load of 30 or more that is located 55 feet or more above the lowest level of fire department vehicle access.
📋 Code
IBC 1015.1 — Exit and Exit Access Doorways Required
Two exits or exit access doorways required from any space where occupant load exceeds the table values. Spaces with occupant load exceeding 500 require a minimum of 3 exits. Spaces exceeding 1,000 require 4 exits.
📋 Code
IBC 1017.2 — Exit Access Travel Distance
Maximum travel distance from any point in a building to an exit shall not exceed 200 feet unsprinklered or 250 feet sprinklered for most occupancies. Specific occupancies have modified limits.
📋 Code
IBC Table 601 — Fire-Resistance Rating Requirements
Specifies minimum fire-resistance ratings for structural elements based on construction type (Type I through V). Type IA requires 3-hour rated structural frame, 2-hour floors, and 1.5-hour roof.