NEC Article 230 — Services

Updated Mar 26, 2026
Service entrance requirements: overhead/underground, disconnecting means, overcurrent protection, grounding.

NEC Article 230: 230.23 overhead service drop clearances: 10ft above grade, 12ft above driveways, 18ft above public roads. 230.32 underground service lateral: min 12in cover under building, 24in under driveways. 230.70 service disconnect: max 6 disconnects or single main breaker, readily accessible, outside or nearest point of entrance. 230.79 rating: min 100A for single-family, min 60A for individual dwelling unit. 230.95 ground-fault protection required for services >1,000A, 277/480V. 230.82 service equipment: suitable for service entrance, rated for available fault current. Service entrance conductors: per Table 310.16. Grounding electrode system per Article 250.

TAGS
NECservice-entranceoverheadundergrounddisconnectgrounding
DETAILS
code year
2023
code system
NEC
code section
Article 230
RELATED KNOWLEDGE
📋 Code
IBC 903.2.1 — Group A Occupancies (Sprinkler Requirements)
Automatic sprinkler system required throughout buildings with Group A occupancy where fire area exceeds 5,000 square feet, or overall building area exceeds 12,000 square feet, or occupant load of the fire area exceeds 300.
📋 Code
IBC 903.2.7 — Group M Occupancies (Retail Sprinkler Requirements)
Automatic sprinkler system required in Group M (mercantile) occupancies where fire area exceeds 12,000 square feet or building is more than three stories above grade.
📋 Code
IBC 903.2.11.3 — Buildings 55 Feet or More in Height
Automatic sprinkler system required throughout buildings with a floor level having an occupant load of 30 or more that is located 55 feet or more above the lowest level of fire department vehicle access.
📋 Code
IBC 1015.1 — Exit and Exit Access Doorways Required
Two exits or exit access doorways required from any space where occupant load exceeds the table values. Spaces with occupant load exceeding 500 require a minimum of 3 exits. Spaces exceeding 1,000 require 4 exits.
📋 Code
IBC 1017.2 — Exit Access Travel Distance
Maximum travel distance from any point in a building to an exit shall not exceed 200 feet unsprinklered or 250 feet sprinklered for most occupancies. Specific occupancies have modified limits.
📋 Code
IBC Table 601 — Fire-Resistance Rating Requirements
Specifies minimum fire-resistance ratings for structural elements based on construction type (Type I through V). Type IA requires 3-hour rated structural frame, 2-hour floors, and 1.5-hour roof.
← Back to Knowledge Garden